Pump Fault – Initial Troubleshooting (VFD / motor)
This guide describes a systematic, field-proven approach for troubleshooting pump, motor, and drive-related faults on LiqTech filtration systems. It applies to centrifugal pumps driven by VFDs and protected by motor protection devices.
When to use this guide
Use this guide when:
-
A pump fault alarm is active on the HMI
-
The pump does not start when commanded
-
The pump trips during ramp-up or shortly after start
-
The VFD shows a local fault
-
A motor protection device or breaker has tripped
Preconditions and safety
-
The system should normally be in STOP state
-
Live testing may be required to observe pump behavior during start
-
Troubleshooting shall only be carried out by competent personnel with:
-
Electrical knowledge
-
Process understanding
-
Familiarity with rotating equipment
-
-
Always ensure:
-
The pump is not running dry
-
The pump is not running against a closed valve
-
Strainers are not blocked
-
-
Follow site-specific lock-out / tag-out procedures when required
Typical symptoms
-
Pump does not start
-
Pump starts briefly and trips
-
Repeated trips after reset
-
VFD shows a local fault
-
HMI shows pump fault or network communication alarm
-
Pump runs but delivers no flow
Step-by-step troubleshooting procedure
1. Check the obvious first (very important)
Before deeper troubleshooting, always verify:
-
Has anything tripped in the electrical cabinet?
-
Motor protection device
-
Circuit breaker
-
-
Is the pump drive powered?
-
Does the VFD display show a local fault or alarm?
-
Has the fault been:
-
Reset locally on the VFD
-
Reset on the HMI
-
👉 A large share of reported pump problems are resolved at this stage.
2. Can the pump rotate freely? (early and critical check)
Before electrical measurements or parameter checks:
-
Verify the pump shaft can rotate freely by hand
-
Check for:
-
Mechanical blockage
-
Seized bearings
-
Foreign objects in the pump
-
👉 If the pump cannot rotate freely, do not proceed with electrical troubleshooting.
3. Distinguish local VFD fault vs. network communication alarm (critical)
Local VFD fault (must be cleared first)
-
A fault is visible on the VFD display
-
The VFD is not operational
-
The pump will not run until the fault is cleared locally
Action:
-
Clear all local VFD faults
-
Ensure the VFD is:
-
Powered
-
Fault-free
-
Ready for operation
-
👉 A VFD must be fault-free before network communication can be expected to work.
Network communication alarm (HMI)
-
The VFD may be electrically healthy
-
Communication between PLC and VFD is lost
-
Common on daisy-chained VFD networks
-
A powered-down or faulted drive can block communication for others
Action:
-
First verify the VFD is powered and fault-free
-
Check that Ethernet connectors are correctly seated
-
Verify the IP address matches the electrical documentation
-
Inspect network cables and connectors for damage
-
Only after this, proceed with further network diagnostics
👉 A network alarm does not necessarily indicate a pump or motor fault.
4. Observe how the fault occurs
If the fault persists, observe:
-
Does the pump:
-
Not start at all?
-
Start and trip immediately?
-
Trip during ramp-up?
-
-
Does the fault appear:
-
Only on start command?
-
After a few seconds?
-
Together with other pump or network alarms?
-
👉 Fault timing is often the fastest diagnostic clue.
5. Mechanical and process checks
Confirm that the pump is not being forced to operate under unfavorable conditions:
-
Ensure the pump is:
-
Properly primed
-
Not running dry
-
Not running against a closed discharge valve
-
-
Check:
-
Suction strainer condition
-
Blockages upstream or downstream
-
6. Controlled low-speed test from HMI (recommended)
The pump can be operated at low speed directly from the HMI.
Procedure:
-
Select the pump on the HMI
-
Enter a low speed setpoint (e.g. 5%)
-
Start the pump briefly
Use this test to:
-
Verify the pump is able to run
-
Confirm correct rotation direction
-
Observe abnormal noise or vibration
Correct rotation direction:
-
The pump shall rotate clockwise
⚠️ Only perform this test when it is confirmed that the pump is not running dry and not operating against a closed valve.
7. Electrical supply and motor checks
If mechanical and process conditions are acceptable:
-
Verify all phases are present
-
Check for:
-
Phase loss
-
Phase imbalance
-
-
Confirm sufficient power supply:
-
Especially important with DG (diesel generator) supply
-
Ensure generator capacity and voltage stability
-
-
Inspect motor cables and terminals for overheating or damage
⚠️ Electrical checks shall only be performed by qualified personnel.
8. VFD parameter and protection checks
If the VFD shows a local fault:
-
Read and note the exact fault code
-
Verify:
-
Motor rated current
-
Voltage
-
Frequency
-
Acceleration / ramp-up time
-
-
Check for:
-
Overcurrent
-
Torque limit
-
Stall or overload faults
-
👉 Ramp-up settings should only be adjusted after mechanical and process conditions have been verified.
9. Reset and verify
After corrective actions:
-
Reset:
-
Motor protection device
-
Local VFD fault
-
HMI alarm
-
-
Allow the system to stabilize for a few minutes
-
Start the pump and observe:
-
Ramp-up behavior
-
Current draw
-
Flow response
-
Field insight – most common root causes
In practice, pump faults are most often caused by:
-
Mechanical blockage or seized pump
-
Incorrect rotation direction
-
Dry running
-
Closed discharge valve
-
Blocked strainer
-
Phase loss or unstable power supply
-
Insufficient generator capacity
Actual motor or VFD hardware failure is less common.
Field insight – multiple pumps affected
If multiple pumps show faults or communication alarms at the same time:
-
Check common power supply
-
Check generator load and stability
-
Check the VFD communication chain
👉 Multiple pump issues usually indicate a system-level problem.
When to stop and contact LiqTech Service
-
If pump trips persist after mechanical, process, and supply checks
-
If VFD fault codes indicate internal drive failure
-
If network communication faults cannot be cleared
-
If pump operation poses a safety risk
Alarm ID references – Pump Fault / Pump Trip / Pump Not Running (examples)
The following alarm IDs are non-exhaustive examples of pump-related alarms observed across different LiqTech Crossflow systems.
They are provided to help support agents recognize the alarm type when a customer references a specific alarm number.Other alarm IDs with similar alarm texts may exist depending on system generation and project configuration.
MK6 – Numeric alarm IDs
Pump motor / protection / overload
21
22
23
24
25Pump not running / no feedback
68
69
70
71
72Pump trip during operation
118
119
120
121
122Pump / drive fault (general)
178
179
180
181MK6 alarms typically repeat per pump and per module.
MK8 / project-based systems – D-series
Pump fault / motor protection
D0004
D0101
D0102
D0201
D0303
D0304
D0417
D0418
D0419
D0601Pump not starting / pump stopped
D0203
D0204
D0501
D0502
MK8 / FM01 – F-series
Pump fault / drive fault
F0120
F0121
F0122
F0123Pump communication / network
F0130
F0131
F0132👉 Root cause differentiation happens inside the guide, not via alarm selection.