Transmitter Signal Fault – Initial Troubleshooting (4–20 mA)
This guide describes a systematic, field-proven approach for troubleshooting transmitter faults on LiqTech filtration systems. It applies to pressure, flow, level, temperature and other transmitters.
When to use this guide
Use this guide when:
-
A transmitter alarm is active
-
The HMI shows out-of-range values
-
The PLC receives no, unstable, or unrealistic signal
-
Measured values do not match expected process conditions
Preconditions and safety
Before starting troubleshooting:
-
The system must be in STOP state
-
Troubleshooting may be performed with the process live, as this is often the fastest way to isolate the fault
-
Live troubleshooting shall only be carried out by personnel with sufficient electrical and process know-how
-
Where possible, troubleshooting should be performed under 24 VDC only (LAUS – Low Voltage DC)
⚠️ Always follow site-specific safety procedures.
Typical symptoms
-
Fixed minimum or maximum reading
-
Sudden signal spikes or dropouts
-
No signal detected in PLC
-
Alarm reappears shortly after reset
Step-by-step troubleshooting procedure
1. Eliminate or assess process influence
-
If possible, isolate or depressurize the transmitter
-
Alternatively, observe whether the measured value behaves plausibly under known stable process conditions
2. Check the transmitter locally
-
Inspect the transmitter for physical damage or contamination
-
Check local display or status indicators (if available)
-
Verify correct supply voltage (typically 24 VDC)
-
If feasible, dismount the transmitter and verify that it reads 0 at atmospheric pressure (or equivalent reference condition)
3. Swap transmitter or components to move the fault (fastest isolation step)
This is often the most efficient troubleshooting method.
-
Replace the suspected transmitter with a known-to-be-good transmitter from another position in the system
-
Observe on the HMI whether:
-
The fault moves to the new position
-
Or remains at the original position
-
If applicable:
-
Swap transmitter hats / electronics between two nearby transmitters (if cable length allows)
-
Observe whether the fault follows the swapped component
👉 If the fault moves, the swapped component is defective.
4. Inspect wiring and signal path (end-to-end)
If the fault does not move, inspect the entire signal path, not just a single section.
The signal path typically includes:
-
Transmitter terminals
-
Transmitter hat / connector
-
Cable gland
-
Field cable
-
Terminal block (input side)
-
Terminal block (output side)
-
PLC I/O card
Checks to perform:
-
Inspect all terminals for loose or intermittent connections
-
Measure continuity from transmitter terminals all the way to PLC input
-
Be aware that faults may exist:
-
Between transmitter and hat
-
Between hat and cable
-
Inside the cable
-
Between cable and terminal block
-
Between terminal block and PLC I/O card
-
5. Measure and simulate signal using test equipment
Multimeter checks
Using a multimeter:
-
Continuity test (“buzz”)
-
Verify uninterrupted signal path conductor-by-conductor
-
-
Voltage check
-
Confirm correct 24 VDC supply at transmitter terminals
-
-
Current measurement (if applicable)
-
Verify actual loop current corresponds to expected signal value
-
⚠️ Ensure the multimeter is correctly configured before measuring current in-loop.
I/O tester (recommended)
An I/O tester can be used to:
-
Simulate a 4–20 mA signal
-
Inject a known signal at:
-
Transmitter terminals
-
Terminal block
-
PLC input
-
👉 This allows verification of wiring and PLC input independent of the transmitter.
6. Verify PLC I/O card and channel
-
Confirm the PLC I/O channel responds correctly to a simulated signal
-
Swap to a spare I/O channel if permitted
-
Inspect I/O card diagnostics and status indicators
7. Reset and verify on HMI
Whenever a change is made:
-
Press “Reset” on the HMI
-
Observe whether:
-
The alarm clears
-
The signal updates correctly
-
👉 Many alarms will not clear until a reset is performed after the fault condition is removed.
Common root causes
-
Defective transmitter electronics or hat
-
Broken or intermittent wiring
-
Loose terminals or connectors
-
Faulty PLC I/O channel
-
Missing reset after signal restoration
When to stop and contact LiqTech Service
-
If the fault persists after transmitter/component swapping and signal simulation
-
If multiple transmitters show similar behavior
-
If signal instability affects control logic or system safety
💡 Note
After replacing or swapping transmitters, always verify correct type, range, and scaling in PLC and HMI.
⚠️ Field insight – multiple transmitters showing abnormal signals
If multiple transmitters suddenly display abnormal or implausible signals at the same time, this often indicates a shared root cause rather than individual transmitter failures.
In such cases:
-
Review the electrical documentation to determine whether the affected transmitters are connected to the same PLC I/O card
-
Check the I/O card status LEDs and diagnostics
-
Verify whether the I/O card has lost indication (e.g. no diode / status light)
👉 If several coinciding faults originate from the same I/O card, troubleshooting should start at the I/O card, not at individual transmitters.
This approach can significantly reduce troubleshooting time and prevent unnecessary component replacement.
Transmitter Signal Fault – Alarm ID references (examples)
The following alarm IDs are non-exhaustive examples of transmitter signal–related alarms observed across different LiqTech Crossflow systems.
They are provided to help support agents recognize the alarm type when a customer references a specific alarm number.
Other alarm IDs with similar alarm texts may exist depending on system generation and project configuration.
FTxx – Flow Transmitters
Examples include:
-
MK6: 30, 31, 32, 76, 77, 78, 127, 128, 129, 225
-
MK8 (D-series): D0007, D0501
-
MK8 (F-series): F0109, F0110, F0111, F0112, F0140
These alarms typically indicate missing, unstable, or implausible flow signals.
PTxx – Pressure Transmitters
Examples include:
-
MK6: 24, 25, 26, 27, 28, 29, 70, 71, 72, 73, 74, 75, 123, 124, 125, 126
-
MK8 (F-series): F0107, F0138, F0139
LTxx – Level Transmitters
Examples include:
-
MK6:
-
34 (Permeate tank)
-
131 (Permeate tank)
-
197 (Concentrate tank)
-
204 (Reject tank)
-
223 (Precipitation tank)
-
-
MK8 (D-series): D0006, D0502
TTxx – Temperature Transmitters
Examples include:
-
MK6: 33, 130
-
MK8 (F-series): F0108
These alarm IDs are references only.
The troubleshooting steps in this guide may also apply to other alarms with texts indicating transmitter signal faults, such as missing signal, out-of-range values, or unstable measurements.